Promat Technical Support
Contact our technical support team with your questions on passive fire protection solutions, our products and systems or installation advice.
Intumescent coating, often referred to as intumescent paint, is one of the easiest and most efficient ways to protect load bearing elements of buildings against fire. Intumescent coating delays the collapse of the structure through insulating the structural elements (columns, beams, floors and roofs) that support the building, thus helping achieve fire resistance levels specified in terms of time. Therefore it fulfills with the highest priority of passive fire protection, preventing the collapse of the building, allowing the time for safe evacuation of people from it, and making it safer for the emergency services and rescue team.
Intumescent coating are an increasingly used way of providing passive fire protection to the load-bearing structures, especially structural steel, which is becoming more and more popular in modern architectural design of both industrial and commercial buildings. As a means of fire protection, it presents several advantages:
Intumescent is a reactive coating which swells as a result of heat exposure, thus increasing in volume and decreasing in density. Specifically, an intumescent paint is a coating that reacts to heat by swelling in a controlled manner to many times its original thickness, producing a carbonaceous char formed by a large number of small bubbles that act as an insulating layer to protect the substrate.
The scope of intumescent products is the prevention of the structural collapse of the building, which can occur if load bearing steel elements reach a critical state.
For steel, this is linked to the critical temperature, defined as the temperature at which the load bearing capacity becomes equal to the effect of the applied loads (so the steel element is very close to the collapse). Critical temperature of steel can vary from 350 °C to 750 °C, depending mainly on the loading scheme, but in most of the cases between 500 °C and 620 °C.
For concrete, critical state is linked to the critical temperature of the reinforcing bars (normally from 350 °C to 500 °C) and the reaching of a temperature of 500 °C inside the concrete element.
For wood, critical state is linked to the residual section of the timber load-bearing element after burning.
Intumescent paints are always part of a system. For steelworks, the system include an anticorrosive primer and (eventually) a topcoat. For the former, the scope is assuring adhesion to substrate in cold state, anticorrosion protection and stickability of intumescent char formed during fire exposure, while the scope of the latter is aesthetic function and, in case of specific atmospheric aggression, sealer function to prevent early degradation and inactivation of intumescent layer and weathering resistance to end-use conditions.
Before being coated with a compatible primer, steelwork must be prepared according to SA 2.5 Swedish Standard. If that is already the case, it must be cleaned and free from grease, oil, rust, dirt or any other contaminant that may inhibit the bonding.
Compatible primers, tested with the main Promat products are:
The preparation for concrete and timber depends on the physical state of the support. For more information, contact our technical department.
For speed and quality of finish, intumescent coatings are preferably spray applied with airless paint equipment. Brush and roller application may also be possible.
The dry film thickness and quantity of material required for a certain fire resistance time (R 30, 60, 90, 120 minutes or more) depends upon various factors.
Dry film thickness of intumescent products for structural steel is determined by the following factors:
During the application, it is necessary to frequently measure the wet film thickness (WFT) with a wet film thickness gauge.
To determine dry film thickness (DFT) based on the wet film thickness (WTF), it is necessary to multiply the WFT with a specific number that is different from product to product. For Promat’s product range, the value is between 0,68 and 0,7 (see specific product data sheet for more information).
The maximum thickness that can be applied for each coating varies by product as well as related consumption (TSR: theoretical spread rate).
Following the sufficient period of drying, a survey of dry film thickness should be carried out using a suitable calibrated gauge. An electromagnetic induction instrument with a statistical function to store readings and calculate their averages is most useful. Where dry film readings include a primer and/or topcoat, allowance must be made for these coatings and subtracted from the total reading.
Intumescent paint for normal interior application can be used without any additional decorative top layer. Adding a topcoat is necessary for exterior semi exposed or high ambient humidity applications.
Nature of the environment to which the coatings will be exposed may affect their durability or their performance in a fire situation. If necessary, a topcoat must be applied to the surface of the intumescent coating, either as a protection against environment degradation or for decorative purposes.
The topcoat should be specified based upon the intended use of the system and the environmental conditions.
The following use categories are defined for the fire protective products according to ETAG 018:
If protected with specific topcoat (depending on the weather condition), intumescent paints can also be applied in high humidity, semi-exposed or exposed conditions.
The main chemical families of topcoat used for environmental protection are:
Intumescent paints can also be used for protecting concrete, in which case the thickness necessary for given fire resistance time is calculated with regard to critical temperature of both the steel reinforced bars (between 350 °C and 500 °C) and the concrete cover (the least distance between the surface of embedded reinforcement and the outer surface of the concrete).
(Especially transparent) intumescent coating can also be used for protection of timber, reducing the fire reaction and improving the fire rating.
Contact our technical support team with your questions on passive fire protection solutions, our products and systems or installation advice.
Find the product datasheets, system brochures, declarations of performance, installation manuals and other documents you need to get the job done.
Follow #Promat on social media: